Server Technology Transfer Switch PDU

Tech Specs

Transfer Switch CDU
PTTS-H008-0-02 100-120V
50/60Hz
or
208-240V
50/60Hz
20A
or
16A
NEMA 5-20P,
L5-20P or
IEC 60320/C13
Cord Set, 10 ft (3m)
(8) IEC 60320/C13

1.75" x 8" x 17"
(44x203x432mm)

Additional Features and Specifications
Standards
> cTUVus – UL 60950-1-2003
> CAN/CSA 22.2 No. 60950-1:2003
> TUVGS – EN 60950-1:2001
> FCC Class A, Part 15
> CE
> EMC-EN 55022 Class A, EN 55024

 Branch Circuit Protection
>Compliant to UL 60905-1
Fail-Safe redundancy between Primary and Secondary power sources.
Primary-Select switch to designate primary power source;
Range-Select switch to designate operating range (voltage). 
Transfer Range
Nominal Pull In Drop Out
110-120V 90V 12V
208-230V 173V 23V
Indicator LEDs -Confirms power supplied to outlets
-Identifies condition as primary power source or secondary power source supplying power to outlets
Voltage Range Select -Supplies either 100-120V or 208-230V AC voltage ranges
-120V and 230V equipment cannot be intermixed
-All power input feeds must be removed prior to selecting/altering operating range
-Remove Range Select faceplate covering to select appropriate voltage
-Lucite window allows visual confirmation of voltage range
-Switch in “up” position designates 208/230V
-Switch in “down” position indicates 110/120V
Mechanical Integrity -Dual-brace cable retainer brackets on power input feeds
-Clip-style cable-retention retainer brackets at each power outlet receptacle
-Adjustable mounting for front or rear panel, flush or recessed mounting